Agilent Technologies DP111 Especificações Página 205

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 452
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 204
Section 5 Maintenance PM861/PM864/PM865/PM866/PM891 Unit in Redundant Configuration
3BSE036351-510 A 205
PM861/PM864/PM865/PM866/PM891 Unit in Redundant Configuration
B(attery) LED is flashing Battery voltage (Internal or External) is below 3.1 V
or non-existent.
Install new battery.
External battery cable disconnected.
Connect external battery cable.
See Fault-Finding Ta bl e 30 on page 208.
Table 27. PM861/PM864/PM865/PM866/PM891 Redundant Configuration –
Fault-Finding Procedure
Fault Possible Cause and Corrective Action
DUAL LED is OFF on both
CPUs
The CPUs are in the process of being re-started
or configured. Allow time for this to finalize.
RCU Link Cable disconnected.
Connect the RCU Link Cable.
Different Control Software in the two CPUs.
Upgrade the CPUs with the same control
software.
Fault LED is ON Check controller log.
Table 26. PM8xx – Fault-Finding Procedure (Continued)
Fault Possible Cause and Corrective Action
Vista de página 204
1 2 ... 200 201 202 203 204 205 206 207 208 209 210 ... 451 452

Comentários a estes Manuais

Sem comentários