Agilent Technologies DP111 Especificações Página 181

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 452
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 180
Section 4 Operation AC 800M Controller (PM8xx)
3BSE036351-510 A 181
Switches and Push buttons
Connectors
Table 21. PM8xx – Switches and Push buttons
Marking Type Function
INIT Manual Push
button
Initiates
1. Cold Restart if INIT is held less than 2.5
seconds.
2. Controller Reset if INIT is held more than
3 seconds.
If INIT is pushed on the Primary CPU in
redundant configuration a switchover to the
backup CPU will be initiated.
Table 22. PM8xx/TP830 and PM891 – Connectors
Marking Function
L+
L–
SA
SB
External Power Supply Connection
+24 V DC supply
0 V
Redundant Power Supply monitoring input
Redundant Power Supply monitoring input
SH
B+
B–
External Battery Connection
Shield (Screw Connector)
Battery Positive (Screw Connector)
Battery Negative (Screw Connector)
Tx
Rx
ModuleBus Connection
Data Transmission Port (Optical)
Data Reception Port (Optical)
Note – Duplex or Simplex optical cables may be used.
MODULEBUS
(1)
Provides expansion of I/O unit capability.
Vista de página 180
1 2 ... 176 177 178 179 180 181 182 183 184 185 186 ... 451 452

Comentários a estes Manuais

Sem comentários