Fault-Finding Procedures Section 5 Maintenance
204 3BSE036351-510 A
Fault-Finding Procedures
The following sections describe elementary fault-finding procedures. For complete
instructions contact ABB Support.
PM8xx Processor Unit in Single CPU Configuration
Table 26. PM8xx – Fault-Finding Procedure
Fault Possible Cause and Corrective Action
F(ault) LED is ON Controller Re-start, (INIT), in progress.
Wait for Controller restart to finalize.
Missing firmware.
Upgrade firmware.
Firmware upgrade in progress.
Wait for FW upgrade to finalize.
Firmware upgrade failure.
Use serial FW upgrade.
Missing TB852
Check TB852 connection
(PM861, PM864, PM865).
Other
Check controller log.
F(ault) LED is flashing Firmware upgrade in progress:
Wait for FW upgrade to finalize.
Other
Check controller log.
R(un) LED is OFF No application loaded in the Controller.
Download application.
Controller application failed.
Restart Controller (INIT push button).
Download application.